Startseite » Products » ACTIVE ENERGY MANAGEMENT DEVICES » Accessories for Active Energy Management Devices » 24 Volt Emergency Power Supply NEV
The 24 Volt Emergency Supply NEV is used to supply the 24 V DC link with mains independent electrical voltage.
Rated current
6A ((up to 150VA) for failure operation)
Rated current
5A ((up to 120VA) for mains operation)
Input voltage (terminal X2)
22 … 26 VDC
Contact
Michael Koch GmbH
Phone: +49 7251 96 26-200
Environmental conditions:
Parameter | Value |
---|---|
Environmental temperature | -10° C to +85° C (transport, storage) |
0°C up to +40°C (operation) | |
Relative humidity | <95% (transport, storage) |
<85% (operation) | |
Cooling type | Air cooled (convection) |
Protection level | housing IP20 |
Degree of pollution installation location | 2 |
Technical data NEV:
Parameter | Value |
---|---|
Input voltage (terminal X2) | 22 … 26 VDC |
Rated current Inenn | 6A ((up to 150VA) for failure operation) |
5A ((up to 120VA) for mains operation) | |
Standby power dissipation | < 1 W |
Overvoltage category | III (altitude up to 2000 m above sea level) |
II (altitude about 2000 m above sea level) | |
Immunity to interference | Industries in accordance with EN 6100-6-2-2005 and EN 6100-6-4-2007 |
Dimensions H x W x D | 275 x 90 x 60 mm |
Weight | approx. 1.0 kg |
In the event of major voltage fluctuations or power failure, the 24 Volt emergency power supply, or NEV for short, supplies its secured 24 Volt circuit with power. How long it can do this depends primarily on the load and the energy available from the supply unit of the energy management device Pxt. Also the settings of
the supply unit have an influence on the duration of the supply of electrical energy.
However, the NEV is not designed for continuous operation. The power supply that provides the continuous supply is normally connected as a power source to the NEV. The consumers on the circuit to be secured are connected to the NEV. This is automatically used to teach The NEV about the externally connected voltage and thus to support the voltage level.
The 24 Volt Emergency Supply NEV is used to supply the 24 V DC link with mains independent electrical voltage. For this purpose, the NEV makes use of the energy of a supply unit, namely the dynamic energy management device Pxt.